1. What this package provides
Documentation/OpenPLC/EQSP32

EQSP32 OpenPLC User Manual

This guide is for users who want to write IEC 61131-3 programs in OpenPLC Editor and run them on an Erqos EQSP32CE, including EQX expansion modules. It covers installation, system layout, pin modes, expansion modules, Modbus networking, and common pitfalls.

Package 1.0.0EQSP32 library v1.6.0Revision 102226
EQSP32 IIoT logic controller, front view with its terminals
1.0.0Package versioncom.erqos.eqsp32
v1.6.0EQSP32 libraryIncluded in the package
4.3.0+OpenPLC EditorTested with 4.3.2

1. What this package provides

Figure 1 - EQSP32 with OpenPLC system overview
Figure 1: OpenPLC Editor and EQConnect work with the EQSP32CE and chained EQX modules.

Once installed, OpenPLC Editor can:

  • Select EQSP32CE as the compile/upload target
  • Configure the EQSP32 main-unit terminals and up to 15 EQX modules in one place (System Layout)
  • Compile and upload PLC programs through the official EQSP32 Arduino library

The package carries its own copy of the EQSP32 library (precompiled). OpenPLC compiles every EQSP32CE project with that copy, even when another EQSP32 library version is installed on the PC, so a given package version always builds with the library it was tested with. A newer library reaches OpenPLC users with a new package version.

Because I/O goes through that library, these continue to work alongside the PLC runtime:

  • BLE provisioning with the EQConnect mobile app
  • Automatic Wi-Fi / Ethernet connection

There is no separate Pin Mapping table for this board. All I/O is configured under Configuration → System Layout.

2. Prerequisites

ItemRequirement
OpenPLC Editor4.3.0 or newer (Windows; tested with 4.3.2). Start it once before the trust patch.
Node.jsRequired once, to run the trust-patch script
USBUSB cable to the EQSP32CE for first upload (COM port)
InternetFor the trust patch, and for the first build (the editor downloads the ESP32 core 2.0.17 and RadioLib 7.7.1)

The editor installs the ESP32 Arduino core 2.0.17, which the EQSP32 needs, by itself on the first build.

Build folder: the trust patch also moves OpenPLC’s Arduino folder to C:\EQSP32-OpenPLC, so builds work with any Windows user name. Files downloaded before the patch are downloaded again on the next build (a few minutes, once).

3. Installing the board package (customer kit)

The OpenPLC Editor only accepts cryptographically signed board packages. Until Erqos is an official signed vendor in the editor, the download kit includes a one-time editor patch that adds Erqos’ public signing key.

Figure 2 - Install flow from the Erqos website kit
Figure 2: Download the kit, extract it, run the one-time trust patch, add the .vpp, then select EQSP32CE.

For step-by-step commands aimed at website downloads, follow INSTALL.md in the kit (extract the ZIP, close OpenPLC, run the Node trust patch, then add the .vpp in the editor’s Package Manager: Device → Configuration → Device list → + Install additional boards… → Installed → +).

3.1 Contents of the download kit

com.erqos.eqsp32-1.0.0.vpp     Signed board-support package (includes the EQSP32 library)
INSTALL.md                     Quick install for website customers
USER_MANUAL.html               This manual (open in a browser)
RELEASE_NOTES.md               What is new in this version
tools/patch-editor-trust.mjs   One-time editor trust, short build path and display patch
tools/migrate-project-config.mjs  Fixes projects saved with an older package (section 13)
keys/eqsp32-dev.pub.pem        Public key only (safe to share)
examples/                      One example project per language (section 11.1)
LICENSE.md                     License of the package and the EQSP32 library

3.2 After an OpenPLC Editor update

If the editor reinstalls or updates itself, the trust patch may be lost. Close the editor, extract the kit again if needed, and re-run the trust patch from INSTALL.md. Reinstall the .vpp if EQSP32CE is missing.

4. Creating a project and selecting the device

  1. Create or open a project in OpenPLC Editor.
  2. Open Configuration and select device EQSP32CE.
  3. Open Configuration → System Layout.

You should see:

  • Slot 0 — EQSP32 (fixed; cannot be removed)
  • Optional expansion slots (Add module) for EQX modules

If slot numbers show as 1, 2, 3… instead of 0, 1, 2… the trust/display patch was not applied. Behavior still works; only labels differ.

5. System Layout — how EQSP32 I/O is organized

Figure 3 - System Layout slots match the physical EQX chain
Figure 3: Slot 0 is the fixed EQSP32. Slots 1-15 are EQX modules in physical bus order.
Figure 4 - I/O Mapping Mode, address, and alias
Figure 4: Bind PLC variables with aliases. IEC addresses are auto-assigned and may reflow when Modes change.

5.1 Slot 0 — EQSP32 main unit

ConnectorChannelsCapabilities
X1ADIO1–ADIO8Digital and analog modes
X2DIO9–DIO16Digital, power PWM, relay, pulse counter

Each row in the I/O Mapping table has:

  • Channel — faceplate / connector name
  • Type — IEC class (digital/analog in/out)
  • Mode — electrical function (EQSP32 library mode)
  • IEC Address — auto-assigned (%IX, %QX, %IW, %QW)
  • Alias — friendly name for PLC variables

5.2 Slots 1–15 — EQX expansion modules

Add modules in the same physical order they are chained on the EQSP32 expansion bus. The EQSP32 finds each module by its place in the chain, so the slot order must match.

Supported modules in 1.0.0:

ModuleRole
EQXIO10× digital I/O (DIN / SWT / POUT)
EQXAI8× analog in (AIN / CIN / TIN)
EQXRA8× relays + 2× 0–10 V analog outs
EQXTC6× thermocouple
EQXPT2× PT100 (2/4-wire or 3-wire per channel)
EQXPH1× pH
EQXHI10× isolated AC/DC voltage-presence inputs, frequency and quality per input

The number of modules is also limited by OpenPLC’s I/O limits (see §12).

5.3 Configuration section (per slot)

Below each slot’s I/O Mapping table is a Configuration panel. Only parameters relevant to selected modes appear (for example NTC coefficients when a pin is TIN). Module-level settings (PWM frequency, EQXRA watchdogs) appear at the top of that panel.

6. Main-unit pin modes and PLC values

Mode labels always start with the EQSP32 library code.

ModeWhereIECPLC value / notes
DIN (Digital Input)X1/X2%IX0 / 1 — default ADIO1–4
SWT (Switch Input)X1/X2%IX0 / 1 — debounce in Configuration
AIN (Analog Voltage Input)X1 only%IWmillivolts (0–5000) — default ADIO5–8
CIN (Current Loop 4-20mA)X1 only%IWmA × 100 (e.g. 1200 = 12.00 mA)
TIN (NTC Temperature)X1 only%IW°C × 10, signed — use WORD_TO_INT
RAIN (Relative Analog Input)X1 only%IW0–1000 relative to 5 V VOut
PCC (Pulse Counter)X2 only%IWpulses since the previous scan
PCC (Pulse Total)X2 only%ID (DINT)running total, never cleared (§6.2)
QENC A (Quad encoder signal A)DIO9, 11, 13, 15%ID (DINT)encoder position; the next terminal must be QENC B (§6.2)
QENC B (Quad encoder signal B)DIO10, 12, 14, 16%IXTRUE while the encoder counts up
POUT (Digital Output)X1/X2%QXoff / on — default DIO9–12, 15–16
POUT (Power PWM Output)X1/X2%QW0–65535 → 0–100% duty — default DIO13–14
RELAY (Relay Derated Output)X1/X2%QXpull-in then hold; hold % and delay in Configuration

6.1 Main-unit Configuration parameters

ParameterApplies whenNotes
PWM FrequencyAny POUT/RELAY on main unitShared for the whole POUT group (Hz)
Relay SequencerRELAYOff (default): RELAY outputs switched on in the same scan pull in together. On: they pull in one after another, to spread the pick-up current
Switch DebounceSWTMilliseconds
NTC Conversion + coeffsTINBeta, Steinhart-Hart, or Normalized S-H
Pulse EdgePCC, PCC (Pulse Total)Rising, Falling or Both edges
Encoder Signal FormatQENC AA/B x4 (default), x2, x1; pulse + direction; up/down pulses
Encoder DirectionQENC ANormal or Reversed
Relay Hold PowerRELAY/1000 (1000 = 100%)
Relay Derate DelayRELAYms at full power before hold

6.2 Counters and encoders

Pulse totals and encoder positions are 32-bit signed numbers (DINT) at %ID addresses. Declare the variable as DINT, or pick it by its alias.

  • The counters run free. The package never clears a total or a position while the PLC runs (both start at 0 after a restart). To zero one, for example at a home switch, keep a reference value in the program and subtract it:

    IF Home_Switch THEN
      Home_Pos := Conveyor_Pos;          (* remember where "home" is *)
    END_IF;
    Position := Conveyor_Pos - Home_Pos;  (* 0 at home, counts from there *)

    In ladder: one rung with a Home_Switch contact driving MOVE Conveyor_Pos -> Home_Pos, and one rung SUB Conveyor_Pos - Home_Pos -> Position. A pulse total works the same way (Batch := Flow_Total - Batch_Start;).

  • Roll-over is safe. After about 2.1 billion counts a counter rolls over as a normal 32-bit counter (from +2,147,483,647 to -2,147,483,648), and Now - Start stays right across it.
  • An encoder uses a terminal pair: DIO9/10, 11/12, 13/14 or 15/16. Set the first terminal to QENC A (Quad encoder signal A) and the second to QENC B (Quad encoder signal B), and wire the encoder’s signals A and B to them. In the program the first terminal gives the position and the second reads TRUE while the position counts up. The Signal Format in Configuration sets what the B input does: A/B x4, x2 or x1 (counts per signal period), pulse + direction (pulses on the first terminal, direction level on the second, high counts up), or up/down pulses (the first terminal counts up, the second counts down).
  • The build stops with a message when the second terminal of a QENC pair is not QENC B (or QENC B has no QENC A before it), or when more than four terminals and pairs use the counters: PCC (Pulse Counter), PCC (Pulse Total) and QENC pairs share four hardware counters.
  • Power the EQSP32 through VIn when an encoder is connected. On USB power alone the first counts after a pause can be lost.
  • Modbus does not read %ID. To give a position or a total to an HMI or a Modbus master, copy it to a %MD variable every scan (§10):

    Position_MB AT %MD0 : DINT;   (* holding registers 52-53 *)
    ...
    Position_MB := Position;

7. Aliases and IEC addresses (important)

IEC addresses are auto-assigned (lowest free address per class). Changing a Mode can change a channel’s IEC class and reflow addresses.

Always bind PLC variables using aliases, not hard-coded addresses.

Default aliases (when the editor patch is applied):

HardwareExample alias
Main unit ADIO1ADIO_1
Main unit DIO9DIO_9
First EQXIO, DIO3XIO_1_DIO3
Second EQXRA, RL5XRA_2_RL5
First EQXTC, CH1XTC_1_CH1

You may rename aliases; user edits always win. Use letters, digits and _ (the editor does not accept . or spaces in an alias).

Pin names in EQMonitor. A terminal or module channel you rename here gets that name on the EQSP32 when the program starts, so EQMonitor shows it next to the pin (for example Start_Button beside terminal 3). Default aliases are not sent: they only repeat the pin number. Names are set at every start and are not stored in the EQSP32.

8. EQX expansion modules in detail

Channel names include the connector prefix (X1., X2., X3.) to match the module housing.

A module that is missing or stops answering (unplugged, loose cable, module reset): its digital inputs read FALSE, its analog inputs read 0, its temperatures read −32768, and its outputs are not written. Write your program so that FALSE is the safe state of every input that permits motion or heat.

8.1 EQXIO

ChannelsModesPLC
X1.DIO1–5, X2.DIO6–10DIN / SWT / POUT%IX or %QX

SWT debounce appears in Configuration when SWT is selected.

8.2 EQXAI

ChannelsModesPLC
X1.CH1–4, X2.CH5–8AIN / CIN / TIN%IW — mV / mA×100 / °C×10

TIN conversion parameters appear in Configuration (same options as the main unit).

8.3 EQXRA

I/O Mapping (physical terminals only):

ChannelsModePLC
X1.RL1–2, X3.RL3–8RELAY (Relay Output)%QX on/off
X2.AO1–2AOUT or SAOUT%QW 0–65535 → 0–10000 mV

RL1–2 have independent COM; RL3–8 are paired COM (3–4, 5–6, 7–8).

The EQXRA’s internal status values are not PLC channels in this release.

AOUT vs SAOUT

Figure 5 - EQXRA analog outputs AOUT vs SAOUT
Figure 5: AOUT is independent per channel. SAOUT requires both AO1 and AO2 set to SAOUT.
ModeBehavior
AOUTIndependent 0–10 V channel
SAOUTSynchronized AO pair — set both AO1 and AO2 to SAOUT

Mixing AOUT on one channel and SAOUT on the other does not synchronize. In SAOUT, AO1 and AO2 change at the same moment.

EQXRA Configuration (protection)

Figure 6 - EQXRA Configuration protection settings
Figure 6: EQXRA watchdogs and feedback-deviation settings live in the Configuration panel, not as PLC channels.
SettingDefaultMeaning
System WatchdogEnabledIf EQSP32 stops polling the module in time, all relays and AOs disable. Keep enabled.
Relay Watchdog Timeout200 msShared; no relay command within timeout → all relays off. 0 = disabled.
AO1 / AO2 Watchdog Timeout1000 msPer AO; 0 = disabled.
AO1 / AO2 Deviation Threshold + DelayOff (0 mV)Fault when command vs feedback deviate too long.

8.4 EQXTC

ChannelsModePLC
X1.CH1–3, X2.CH4–6TC%IW °C × 10, signed → use WORD_TO_INT; sensor fault = −32768

8.5 EQXPT

ChannelsModePLC
X1.M1, X2.M2PT100 (2/4-wire) or PT100 (3-wire)%IW °C × 10, signed → use WORD_TO_INT; sensor fault = −32768

Pick wiring per channel with the Mode dropdown.

8.6 EQXPH

ChannelModePLC
X1.PH1PH%IW pH × 100 (704 = 7.04)

8.7 EQXHI

ChannelPLCValue
X1.IN1-5, X2.IN6-10%IXTRUE while voltage (AC or DC) is present on the input
FREQ1-10 (optional)%IWmeasured frequency in Hz × 10 (500 = 50.0 Hz); 0 for DC or no input
QUAL1-10 (optional)%IWfrequency quality: bits 0-2 the live code, bit 7 the delayed frequency error

PLC Channels in the Configuration section chooses which rows exist: Inputs, Inputs + frequency, or Inputs + frequency + quality. Choose only what the program needs; each frequency or quality channel uses one analog input address.

Quality codes (bits 0-2): 0 not available (no input), 1 acquiring, 2 bad (off target), 3 marginal, 4 good, 5 excellent, 6 not monitored. Bit 7 (value 128 added) is the delayed frequency error. Test the code with (QUAL MOD 8) = 4 and the error with QUAL >= 128.

Frequency monitoring is set per COM group (IN1-IN5 and IN6-IN10): Target Frequency (0 for DC, or 25 to 1000 Hz), Allowed Deviation (0 switches monitoring off) and Error Delay (0 to 60,000 ms).

9. Working with scaled values in the PLC program

Figure 7 - Value scaling what the PLC number means
Figure 7: Common raw PLC values and their physical meaning.
SignalRaw %IW / %QWHow to interpret
Voltage (AIN)millivoltse.g. 2500 = 2.500 V
Current (CIN)mA × 100e.g. 2000 = 20.00 mA
Temperature (TIN/TC/PT)°C × 10, signedConvert with WORD_TO_INT before using as INT
pH× 100e.g. 704 = 7.04
EQXHI frequency (FREQn)Hz × 10e.g. 500 = 50.0 Hz
PWM duty (%QW)0–65535Maps to 0–100%
EQXRA AO (%QW)0–65535Maps to 0–10000 mV (0–10 V)

Signed temperatures: OpenPLC analog words are unsigned. Negative °C values require WORD_TO_INT (or equivalent) in the program.

Temperature faults: TIN (open or short circuit), TC and PT sensor faults, and a temperature module that is missing, read −32768 after WORD_TO_INT (−3276.8 °C, never a real reading). Test for it before you use the value.

10. Modbus and networking

Since OpenPLC Editor 4.3 the Modbus server belongs to the project, and the package supplies the EQSP32’s ports. Three places:

  1. Device → Network (package screen): switch on Enable network, and choose DHCP or a static address. The EQSP32 library runs the RJ45 Ethernet port and Wi-Fi and switches between them by itself: Ethernet works as soon as the cable is plugged in. For Wi-Fi, enter the network name and password, or leave them empty to use the Wi-Fi set up with the EQConnect app.

    • A static address set here is applied by a network reset: hold BOOT for 3 s (this also clears the Wi-Fi network). Otherwise set the address with the EQConnect app.
    • Keep Ethernet and Wi-Fi both on: no switching; both stay connected. A static address goes to Ethernet, and Wi-Fi uses DHCP. Modbus TCP and the debugger answer on both addresses. Use it, for example, for Modbus on a fixed Ethernet address with Wi-Fi for EQConnect.
    • Disable Erqos IoT: turns off BLE, the EQConnect app, EQMonitor (pin names, forcing) and Wi-Fi. The EQSP32 then works on Ethernet only, with an address from DHCP. The screen hides the settings that no longer apply.
    • BLE advertising time: how long the EQSP32 stays visible to EQConnect and EQMonitor after it starts (default 3 minutes, 0 = always). After that, press BOOT to make it visible again.
  2. Device → Serial (package screen): the Parity of the RS232/RS485 port: None, Even or Odd (8 data bits, 1 stop bit). Many Modbus masters expect Even.
  3. Servers → Modbus server (editor screen): choose RTU, TCP or both, the slave ID, and for RTU the Serial Port and baud rate:

    • RS485_Port: the EQSP32’s RS485 terminals. Set the Modbus master to wait at least 10 ms between a reply and its next request (most masters wait longer by default).
    • RS232_Port: the RS232 terminals.

    The EQSP32 has one serial port, used as RS232 or as RS485: pick one. The USB port belongs to the editor (upload and debugger); a server set to Serial stops the build with a message.

Modbus TCP answers on port 502 (or the server’s port) over Ethernet and Wi-Fi. Set the Modbus master’s timeout to at least 2 s: a few requests per thousand take about 1 s on Ethernet and on Wi-Fi.

Register map (register numbers start at 0):

PLC addressModbusRegisters
%QX outputsCoils%QX0.0 = coil 0, %QX0.1 = coil 1, … %QX1.0 = coil 8
%IX inputsDiscrete inputs%IX0.0 = input 0, … (same numbering as the coils)
%IW inputsInput registers%IW0–%IW31 = 0–31
%QW outputsHolding registers%QW0–%QW31 = 0–31
%MW memory (INT, UINT, WORD)Holding registers%MW0–%MW19 = 32–51
%MD memory (DINT, UDINT, DWORD)Holding registers%MD0–%MD19 = 52–91, two registers each, high word first
%ML memory (LINT, ULINT, LWORD)Holding registers%ML0–%ML19 = 92–171, four registers each, high word first

%ID (pulse totals and encoder positions, §6.2) is not in the map. Copy the value to a %MD variable in the program.

Debugger: always available over USB at 115200 baud; it needs no Modbus settings. With the network enabled the editor also offers the debugger over the network and asks once for the EQSP32’s IP address (EQConnect shows it).

Projects made with package 0.7.x: editor 4.3 does not carry the old Modbus screen settings forward. Set up the Network screen and a Modbus server again.

BLE / EQConnect provisioning remains available whatever the network settings, unless Disable Erqos IoT is on.

11. Compile, upload, and first run

  1. Finish System Layout and program logic.
  2. Select the correct COM port for the EQSP32CE.
  3. Build / upload from OpenPLC Editor.
  4. First compile may take several minutes while core 2.0.17 and RadioLib 7.7.1 download. The EQSP32 library comes with the package and is not downloaded. On the first upload, Windows Firewall may ask about mdns-discovery. It only looks for network-connected boards; uploads over USB work if you deny it.
  5. After upload, the PLC scan runs on the device; use EQConnect if you still need BLE setup.

If compile fails after an editor update, re-apply the trust patch (§3.2) and reinstall the .vpp if needed.

11.1 Example projects

The kit has one example per language in examples/. Copy a folder, open it with Open in OpenPLC Editor, pick the COM port, build and upload. Each README.md has the wiring and what to watch in the debugger and in EQMonitor.

FolderLanguageWhat it shows
examples/ST/EQSP32_ConveyorStructured TextStart/stop, a belt position from an encoder (QENC) and a home switch, a part counter (PCC), values for an HMI over Modbus
examples/Ladder/EQSP32_Start_StopLadder DiagramStart/stop with a set coil and a reset coil, a run lamp
examples/FBD/EQSP32_Fan_TimerFunction Block DiagramA fan with an on-delay (TON) and an off-delay (TOF) timer
examples/IL/EQSP32_Guard_InterlockInstruction ListA motor interlocked with a guard switch, a warning lamp

12. Limits and practical cabinet notes

OpenPLC’s I/O limits (approximate):

  • 56 digital inputs / 56 digital outputs
  • 32 analog inputs / 32 analog outputs

The EQSP32 can address up to 15 EQX modules. Typical DIN-rail cabinets fit fewer modules beside the controller; stay within both the cabinet space and the I/O limits above.

Counters on the main unit: PCC terminals and QENC pairs share 4 hardware counters; the build stops with a message beyond four (§6.2).

13. Upgrading the package / missing channels

If channels disappear from the I/O Mapping table after a package upgrade (for example AO1/AO2 or ADIO1), the project usually still has an old Mode string that the new catalog no longer lists. The editor silently drops those rows.

Fix:

  1. Close the project (or quit the editor).
  2. Run:

    node tools/migrate-project-config.mjs "<path-to-your-project-folder>"
  3. Reopen the project.

The tool writes devices/configuration.json.bak before changing anything.

14. Troubleshooting

Every build message of the package starts with EQSP32:. When a build stops, search the editor’s console for EQSP32: to find the reason among the compiler output.

SymptomLikely causeWhat to do
Cannot install .vpp / signature errorTrust patch not appliedClose editor, run patch-editor-trust.mjs
EQSP32CE missing after editor updateThe update removed the trust patchRe-run the trust patch; reinstall the .vpp if needed
Channel missing from I/O MappingStale Mode in projectRun migrate tool (§13)
Slot numbers start at 1Display patch not appliedCosmetic only; or re-run trust patch
Empty aliasesDisplay patch not appliedEnter aliases manually
Compile errorsAnother ESP32 core versionThe package needs 2.0.17: let the editor install it
Negative temperature looks hugeTreating %IW as unsignedUse WORD_TO_INT
EQXRA AOs not syncing as expectedOnly one AO set to SAOUTSet both AO1 and AO2 to SAOUT (§8.3)
Compile stops with bits/c++config.h: No such file or directoryArduino folder path too longRun the trust patch again (it sets the short path C:\EQSP32-OpenPLC)
Build stops: EQSP32: DIO9 is set to QENC A (Quad encoder signal A): set DIO10 to QENC B ...The second terminal of the encoder pair has another modeSet it to QENC B (Quad encoder signal B) (§6.2)
Build stops: EQSP32: more than 4 counters on DIO9-16 ...Too many PCC terminals and QENC pairsUse at most four (§6.2)
Encoder position a few counts short after a pauseEQSP32 on USB power onlyPower the EQSP32 through VIn
Windows Firewall asks about mdns-discovery on uploadNetwork board discoveryDeny is fine for USB uploads
Build stops: EQSP32: Modbus RTU cannot use the USB port ...The Modbus server’s Serial Port is Serial (USB)Set it to RS485_Port or RS232_Port (§10)
No Modbus register holds an encoder position or a pulse total%ID is not in the Modbus mapCopy the value to a %MD variable (§6.2, §10)
Modbus TCP does not answerNetwork off, or Modbus server without TCPDevice → Network: Enable network; Servers → Modbus: tick TCP (§10)
Modbus RTU answers garbage or nothingBaud rate or parity differ from the masterMatch the server’s baud rate and the Serial screen’s parity to the master
All inputs of a module read FALSE / 0 / −32768Module missing or not answeringCheck the module cable and the slot order (§5.2, §8)
Relays/AOs drop unexpectedlyWatchdog timeoutIncrease timeout or keep commanding outputs each scan

15. What stays with EQConnect / the EQSP32 library

OpenPLC owns the PLC scan and mapped I/O. The EQSP32 library still owns:

  • BLE / EQConnect provisioning
  • Wi-Fi and Ethernet connection

Do not expect OpenPLC’s System Layout to replace EQConnect for device provisioning.

16. Support scope for this package version (1.0.0)

Included:

  • EQSP32CE main unit full Mode set via System Layout
  • EQXIO, EQXAI, EQXRA, EQXTC, EQXPT, EQXPH, EQXHI
  • EQXRA watchdog / feedback-deviation configuration
  • Modbus TCP (Ethernet / Wi-Fi) and Modbus RTU (RS232 or RS485) through the editor 4.3 Modbus server
  • EQSP32 library v1.6.0 bundled in the package
  • Quadrature encoders (QENC, all formats) and the PCC running total (§6.2)
  • Missing-module handling (inputs read FALSE / 0)

Not included / deferred:

  • The EQXRA’s internal status values as PLC channels
  • Thermocouple type selection (library exposes a single TC mode)
  • Listing in OpenPLC Editor’s package catalog (this kit installs with the trust patch)
  • CAN bus (no OpenPLC function blocks for it yet)

Notices

Erqos Technologies P.C. may change products, software, specifications and this document at any time without notice. Always use the latest revision, available at erqos.com.

These products and this document are intended for qualified professionals. The information in this document is provided as is. Erqos Technologies P.C. assumes no liability for its use. Customers are responsible for designing and testing their own applications, including the protection of connected equipment and persons.

For hardware details, see the EQSP32 and EQX module datasheets at erqos.com.