Overview

EQXPH01 Datasheet

pH Sensor Expansion Module for the EQSP32 IIoT PLC Controller.

Version 1.1Revision 102026
EQXPH01 pH meter expansion module for the EQSP32 PLC with BNC probe connector, DIN-rail enclosure

Overview

The EQXPH01 is a compact, easy-to-install pH measurement module designed for seamless integration with the EQSP32 Industrial IoT controller. Fitting into any standard DIN-rail cabinet, this expansion module enhances your automation system’s functionality by adding precise pH monitoring capabilities. With its simple slide-to-connect approach, incorporating pH measurement into both new and existing setups is straightforward and efficient.

The module features a standard BNC connector, allowing quick and secure attachment of a wide range of pH probes. This ensures compatibility with most commercially available probes, making it versatile for various industrial, environmental, and laboratory applications.

The EQXPH01 is automatically detected by the EQSP32 controller upon power-up, functioning as a native peripheral. This plug-and-play capability simplifies setup, allowing users to expand their system with minimal configuration.

The pH module supports an easy 1-point, 2-point or 3-point calibration process using Erqos’ pH calibration utility, ensuring precise and reliable pH measurements tailored to the specific probe being used. The calibration parameters are automatically calculated by the utility and, once stored in the unit, they are used to automatically convert the analog input values into pH measurements.

The visual indicator provides feedback for unit status, ensuring easy monitoring during installation and operation. Firmware updates are simple to apply using the front-facing USB-C port, giving you access to the latest features and improvements. This ensures the module maintains optimal performance and continues to enhance its functionality throughout its use.

Supported by the EQ-AI generative AI model, users can easily generate the necessary code by simply describing their setup and functionality needs. This approach enables quick and seamless integration of the EQXPH01 into new or existing EQSP32-based automation systems, significantly reducing the need for extensive programming knowledge.

Key Features

  • Quick and secure BNC attachment for pH probes
  • Accurate pH measurements with 1-, 2- and 3-point calibration using Erqos’ utility
  • Automatic module detection by EQSP32
  • LED indicator for power and module status
  • Easy firmware updates via front-facing USB-C port
  • Up to 15 pH sensors supported on a single EQSP32 controller
  • Generative AI Coding Assistant trained with EQSP32 Library and EQXPH features
  • Compact, 2SU-wide (36 mm), DIN-rail mount enclosure
  • Fits inside standard DIN-rail cabinets for neat and organized installations
  • IP20 Protection
  • –20 °C to +55 °C operating ambient temperature

Applications

  • Agricultural applications like hydroponics
  • Water quality monitoring in industrial processes
  • Environmental monitoring of pH levels in natural waters
  • Chemical balancing in laboratory applications
  • Wastewater treatment and management
  • Industrial pH monitoring for manufacturing processes
  • Educational projects
  • Smart connected recreational systems like pools and hot tubs

Ordering Information

Part numberDescriptionInputsEnclosure
EQXPH01pH Sensor Expansion Module for EQSP321 × pH probe (BNC)2SU (36 mm) DIN-rail, IP20

Product page and ordering: erqos.com/product/eqxph01

Block Diagram

EQXPH01 block diagram: pH probe on BNC input, amplifier and converter, Cortex-M0+, USB-C calibration port, EQSP32 bus
Figure 1: EQXPH01 block diagram

System Specifications

Section / Features
Power Management
Supplied by the board-to-board connector
pH Probe Connector
Standard BNC connector for secure attachment of pH probes
Compatible with most commercial and professional probes
Measurements
Range 0 to 14 pH
Accuracy ±0.1 pH (after calibration)
Calibration
1-point, 2-point or 3-point calibration for optimized accuracy
Calibration utility available for easy connection and calibration parameter calculation
Indications
Green LED for power indication
Red LED for device status
Enclosure
Easy standard DIN rail push-fit mounting with spring mechanism
IP20
Expandability
Push-fit expansion module mounting
Automatic module detection and characterization
Firmware Update
Front-facing USB-C for easy firmware upgrades
Environment
–20 °C to +55 °C (–4 °F to +131 °F)

Connecting EQXPH

To use the EQXPH pH measurement expansion module, mount it next to the EQSP32 controller on the DIN rail and simply slide it until the board-to-board connector is fully inserted into EQSP32.

The expansion module is powered by the board-to-board connector and does not require an external power supply.

When adding additional modules, it is recommended that the power is disconnected from the system. After adding the expansion modules and powering up the system, EQSP32 will start the automatic detection and indexing process.

For safety and ease of use, it is strongly recommended that a main circuit breaker is used to completely isolate the AC/DC from the grid.

EQXPH01 pH sensor module sliding onto an EQSP32 PLC on a DIN rail, with breaker and 24 V DC supply
Figure 2: Slide EQXPH to connect on EQSP32
EQXPH01 pH expansion module mounted next to an EQSP32 PLC on a DIN rail
Figure 3: Connected EQXPH on EQSP32

Warning

Make sure that the appropriate ground fault circuit breaker, fuses or circuit breakers and any other necessary protective components are used if there is any risk of user electrocution.

Visual Indications

EQXPH01 front panel with BNC pH probe connector, power and status LEDs and Boot button
Figure 4: Front panel: LEDs and Boot button

When the module is connected and the system is powered on, the POWER LED should light up solid green.

If the STATUS LED remains solid red after the automatic detection, it means that the EQXPH module is not communicating with the EQSP32.

During data exchange between the main EQSP32 unit and the EQXPH module, the STATUS LED will be flashing for each transaction.

Power LED (green)

OnPowered on
OffNo power

Status LED (red)

OffNo errors, no communication
Fast FlashingData exchange
BlinkingAuto indexing issue
Blink OffHardware detection failed
OnCommunication error

Pinout

EQXPH01 connectors: BNC input for the pH probe, USB-C port, LEDs and Boot button
Figure 5: EQXPH01 connectors and front panel
BNC
BNC pH probe connector
USB-C
Firmware update port

BNC – pH Probe BNC Connector

The BNC connector on the EQXPH01 is designed for secure and quick attachment of a wide range of commercial and professional pH probes. This single connector allows the connected pH probe to send analog signals to the module for accurate pH measurement.

Calibration may be required when a different brand or model of pH probe is used, ensuring precise readings tailored to the specific probe.

EQXPH01 BNC connector for the pH electrode, front and side views
Figure 6: BNC pH probe connector

Power Distribution

EQXPH’s internal systems are powered by EQSP32’s power management unit via the board-to-board connector.
The board-to-board connector carries the power lines for system operation and the communication bus for allowing the expansion modules to interact with the main EQSP32 unit.

EQXPH’s control unit may also be powered by the front-facing USB-C port. By connecting the pH sensor expansion module via the USB port, the system’s core will be powered on, allowing for easy firmware update without any external power supply.

EQXPH01 power distribution: 5 V, GND and bus from the EQSP32 expansion connector, USB-C for firmware updates
Figure 7: Power distribution

Mechanical Dimensions

All dimensions are measured in mm with a +/-0.1 tolerance.

EQXPH01 dimensions: DIN-rail enclosure 36.3 × 90.2 × 52.5 mm, BNC connector protruding 14.9 mm
Figure 8: Mechanical dimensions: side and front views
EQXPH01 DIN-rail enclosure 3D view with front BNC connector, USB-C port, LED windows and expansion connector
Figure 9: Mechanical dimensions: 3D view

pH Measurements

Equivalent pH Measurement Circuit

EQXPH01 pH input equivalent circuit: probe signal pH+ and reference pH− into a biased amplifier and converter
Figure 10: Equivalent pH Measurement Circuit

The EQXPH module does not have terminal pins, thus the only available channel is the pH measurement from the BNC connector.

The mode of operation is always set as pH sensor (PH) and may only be read by the user, not changed.

This implementation allows for the EQSP32 library functions to be uniform and offer a native-like handling of the expansion modules.

ModeTypeFunction
pH Sensor (PH)InputAnalog

pH Sensor (PH)

When reading the pH sensor value, the returned value may range from 0 to 1400. This integer reflects the measured pH value multiplied by 100, to preserve the two-decimal precision of the sensor.

The module does not compensate the pH for the temperature of the sample. For the best accuracy, calibrate the probe at the temperature of the process.

A module that is not connected reads 0. Check eqsp32.isModuleDetected( EQXPH(ii) ) before using the reading.

Library Reference
Usage
eqsp32.readPin( EQXPH(ii, 1) )

Returns 0 to 1400 for 0 pH to 14.00 pH

ii: number (index) of EQXPH module on the chain (*)

1: EQXPH has only 1 user-available pin, the BNC connector

Macros
CONVERT_PH( ph )

Converts the pH from int pH × 100 to float pH

ph: the value read with eqsp32.readPin( EQXPH(ii, 1) )

(*) For 2 EQXPH modules connected on the main unit, the first one (closer to the main unit) will have an index of 1, the second EQXPH index of 2 etc.
The index refers only to the same type of modules. Different types of modules will be indexed with their own type.

Calibration

When using the EQXPH module for the first time, when replacing the measurement probe, or when the recommended recalibration interval has elapsed, the module must be recalibrated. Calibration ensures that the sensor system accurately converts the raw electrode signal into a reliable pH value.

pH scale 0–14 with the EQXPH01 calibration points: neutral pH 7, acidic and alkaline
Figure 11: pH Scale showing Neutral (Point 1), Acidic (Point 2) and Alkaline (Point 3) calibration points

The calibration process establishes one, two, or three known reference pH points to define the system’s offset and measurement slopes. While a single-point calibration (neutral only) may be sufficient if measurements stay near pH 7.00, it is not recommended for general use. The second point sets the acidic slope correction and the third point sets the alkaline slope correction, providing maximum measurement accuracy across the full pH range.

Calibration Procedure

General Preparation

  • Use fresh, high-quality pH buffer solutions for all calibration points.
  • Rinse the probe with distilled water and gently blot dry with a lint-free tissue between solutions.
  • Allow readings to stabilize fully at each point before saving.
  • Store calibration data in the module and record the calibration date.
  • Repeat calibration periodically, according to probe manufacturer recommendations or your application’s accuracy requirements.

1-Point Calibration (Offset Calibration)

A single-point calibration defines the system offset relative to a neutral pH value (pH 7.00).

Recommended procedure:

  • Immerse the probe in a pH 7.00 buffer solution.
  • Wait until the reading stabilizes.
  • Store the reading as the neutral reference point.
  • The probe does not need to output exactly 0 mV; the module uses the measured value to correct the offset internally.
pH probe in pH 7.00 neutral buffer solution during EQXPH01 calibration
Figure 12: Probe stabilizes in neutral (pH 7.00) calibration solution

Alternative procedure (direct short):

  • To verify or adjust the electronic zero point of the measurement input stage, disconnect the probe and short the BNC connector’s signal pin to the connector’s ground/shield.
  • This should produce a direct input of 0 mV.
  • Store this value as the neutral reference.
  • This method calibrates only the input electronics and does not include probe-specific offsets.
EQXPH01 zero calibration: BNC signal input shorted to its ground shield for the 0 mV reference
Figure 13: Short the BNC connector’s signal input and ground/shield to generate the 0 mV (ideal 7.00 pH) reference

2-Point Calibration (Acidic Slope)

The second calibration point sets the system conversion slope from the probe-generated millivolt (mV) signal to an accurate pH value for the acidic slope.

  • Perform the 1-point calibration procedure (neutral point at pH 7.00).
  • Rinse the probe with distilled water and blot dry with a lint-free tissue.
  • Immerse the probe in a second buffer solution, typically pH 4.01 (acidic reference).
  • Wait until the reading stabilizes.
  • Store this reading as the second calibration point to define the acidic slope.
pH probe in pH 4.01 acidic buffer solution during EQXPH01 calibration
Figure 14: Probe stabilizes in acidic (pH 4.01) calibration solution

Note

If the third calibration point is omitted, the calculated acidic slope should be manually applied to the alkaline slope as well to ensure consistent conversion accuracy across the full measurement range.

3-Point Calibration (Alkaline Slope)

The third calibration point sets the system conversion slope for the alkaline region, providing full-range linearization and improved measurement accuracy for basic pH values.

  • Complete the 2-point calibration procedure (neutral point and acidic slope).
  • Rinse the probe with distilled water and blot dry with a lint-free tissue.
  • Immerse the probe in a third buffer solution, typically pH 9.18 or pH 10.01 (alkaline reference).
  • Wait until the reading stabilizes.
  • Store this reading as the third calibration point to define the alkaline slope correction.
pH probe in pH 9.18 alkaline buffer solution during EQXPH01 calibration
Figure 15: Probe stabilizes in alkaline (pH 9.18) calibration solution

Calibration Utility

The pH calibration utility offers an easy, intuitive UI for monitoring the measurements and pH conversions of the EQXPH module, for easy calibration.

To run the EQXPH Calibration Utility, double-click the .exe file.

First the EQXPH module must be connected on the EQSP32 unit and powered up. While the system is in normal operation, connect it to your laptop or PC via the USB-C cable, refresh the COM port list and select the EQXPH module’s port.

When you press the “Connect” button, the connection indicator will turn green and the module’s firmware version, module name and last calibration date will appear at the top of the window.

EQXPH pH sensor calibration utility: live pH and mV readings, slope calculation and manual configuration
Figure 16: EQXPH Calibration Utility

Measurements

EQXPH calibration utility measurements panel: live 7.82 pH and 2754 mV reading on a 0–14 pH scale
Figure 17: Calibration utility: Measurements

The Measurements section shows the real-time pH value and the raw mV signal from the electrode after amplification. A color gauge below the values provides a quick visual reference of the pH level.

Configurations

EQXPH calibration utility configurations panel: stored offset and acidic and alkaline slopes in mV/pH
Figure 18: Calibration utility: Configurations

The Configurations section displays the module’s current offset, acidic slope and alkaline slope values stored in memory. These values define how the module converts the amplified electrode signal into a calibrated pH reading.

Slope Calculation

EQXPH calibration utility slope calculation panel with reference pH and calculated slopes
Figure 19: Calibration utility: Slope Calculation

The Slope Calculation section automatically calculates the new slope values by comparing the current electrode reading to your reference buffer solution. Enter the buffer’s pH value, let the probe stabilize and the utility will display the calculated slope.

Manual Configuration

EQXPH calibration utility manual configuration panel: force offset, acid slope and alkaline slope
Figure 20: Calibration utility: Manual Configuration

The Manual Configuration section lets you manually enter offset and slope values if you prefer to override the calculated ones. Any parameter set as zero is omitted from the force update. For example, if only offset and acid slope values are non-zero during manual entry, the alkaline slope will remain as is.

Calibration Buttons

Below these sections, there are the three calibration buttons:

EQXPH calibration utility Set Neutral (Point 1) button
Figure 21: Calibration utility: Set Neutral (Point 1) button

Set Neutral (Point 1): Saves the current measured mV value as the neutral offset, “zero” point. Follow the “1-point calibration (Offset calibration)” procedure.

EQXPH calibration utility Set Slope (Point 2 or 3) button
Figure 22: Calibration utility: Set Slope (Point 2 or 3) button

Set Slope (Point 2 or 3): After inserting the probe into a reference solution (Acidic or Alkaline), enter the reference pH value of the solution into the “Reference pH” parameter of “Slope calculation”.

While the probe is stabilizing, the utility will display the calculated slope for this reference buffer. In around 1 to 2 minutes the probe will be stable. By pressing “Set Slope”, the calculated value is stored in the module’s flash memory.

Follow the “2-point and 3-point calibration” procedures.

EQXPH calibration utility Force Manual Values button
Figure 23: Calibration utility: Force Manual Values button

Force Manual Values: Sends any values entered in the Manual Configuration section directly to the module.

After completing your calibration, click “Update Calibration Date” to save the current date in the module’s memory. This helps track when the last calibration was performed.

EQXPH calibration utility connection bar: firmware version, COM port, Connect and Update Calibration Date buttons
Figure 24: Calibration utility: connection bar and Update Calibration Date button

The Log Console at the bottom records all commands, responses, and messages. You can toggle Raw Data to display all incoming lines from the module, enable or disable Auto-Scroll, and use Clear Log to clear the console.

Boot Button & Firmware Update

Boot Button

The boot button is only used for entering the EQXPH module into firmware update/maintenance mode. To enter maintenance mode, disconnect all power sources from the EQXPH module (power down the EQSP32 and disconnect the USB-C from the module). Press and keep the boot button pressed using the pin. Then connect the module via USB-C to your laptop or PC. The module will then be powered on and enter maintenance mode.

Another option is to keep the boot button pressed while sending a reset command to the module via the serial terminal (!RST=1, 115200 baud).

Once the module is in maintenance mode, it will be shown as a storage device. Drag and drop the desired .uf2 firmware file into the RPI-RP2 storage device. The new firmware will be flashed automatically.

Once the update is done, the unit will be automatically rebooted and ready to use.

After powering on the EQSP32 unit, the system will trigger the automatic detection process and the system will be ready for normal operation.

Notices

Erqos Technologies P.C. may change products, specifications and this document at any time without notice. Always use the latest revision, available at erqos.com.

These products and this document are intended for qualified professionals. The information in this document is provided as is. Erqos Technologies P.C. assumes no liability for its use. Customers are responsible for designing and testing their own applications, including the protection of connected equipment and persons.

Revision History

VersionRevisionDateStatusChanges
v1.1Rev10202620 Oct 2026ReleasedUpdated the status LED meaning; added the CONVERT_PH macro.
v1.0Rev10192619 Oct 2026ReleasedFirst released version.